Lecture

changes, that is, below by a few%.
low-power transformers



- electrical losses
- magnetic losses depend on the load factor
The external characteristic of the transformer is the dependence of the voltage of the secondary winding U 2 on the current I 2 . If we ignore the no-load current, then the equivalent circuit of a transformer in nominal mode takes the form shown in Figure 1.

Considering that Z kz = R kz + jX kz , the voltage on the secondary winding of the transformer can be expressed as follows:
(one)
Construct a vector diagram relative to the current vector
as shown in Figure 2.

If the load resistance
active then the voltage
coincides in phase with the current
. Amount
. The magnitude of the applied voltage U 1 = const , it is obvious that when the current changes
, the voltage drop Δ U on the internal resistance of the transformer will also change. That is, the external characteristic has a falling character, as shown in Fig. 2.25.
Comments
To leave a comment
Electrical Engineering, Circuit design
Terms: Electrical Engineering, Circuit design