In power engineering, a single-line diagram (SLD), also sometimes called a one-line diagram, is the simplest symbolic representation of an electrical power system. One line on the diagram usually corresponds to more than one physical conductor: in a DC system the line includes the supply and return paths, and in a three-phase system the line represents all three phases (the conductors are both supply and return circuits owing to the nature of alternating-current circuits).
The single-line diagram is most widely used in power flow studies. Electrical elements such as circuit breakers, transformers, capacitors, buses and conductors are denoted by standardized schematic symbols. Instead of representing each of the three phases with a separate line or terminal, only one conductor is shown.
It is a type of block diagram that graphically shows the paths of power flow between the elements of the system. The elements on the diagram do not represent the physical dimensions or layout of the electrical equipment, but it is common practice to arrange the diagram in the same order, left to right and top to bottom, as the switchgear or other equipment represented. A single-line diagram can also be used to show the general view of cable routing for a PLC control system.
A typical single-line diagram annotated with power flows. The red rectangles denote circuit breakers , the gray lines are three-phase buses and connecting conductors, the orange circle is an electric generator , the green coil is an inductor , and the three overlapping blue circles are a two-winding transformer with a tertiary winding.
The lines on a single-line diagram connect nodes — points in the system that are "electrically distinct" (i.e., a non-zero electrical resistance exists between them). For sufficiently large systems these points are physical buses , so the nodes of the diagram are often called buses . A bus corresponds to a place where power is either supplied to the system (for example, a generator) or consumed ( an electrical load ). The steady state of each bus can be characterized by its voltage phasor ; the state of the system is determined by the vector of voltage phasors for all the buses. In a physical system the state is calculated by power system state estimation ; since the end of the 20th century this process has included direct simultaneous measurements ( synchrophasors ) made with phasor measurement units .
The theory of three-phase power systems tells us that, as long as the loads on each of the three phases are balanced, the system is fully represented by (and therefore calculations can be performed for) any single phase (so-called per-phase analysis ). In power engineering this assumption is often useful, and considering all three phases requires much effort with very little potential benefit. An important and frequent exception is an asymmetric short circuit on only one or two phases of the system.
A single-line diagram is usually used in combination with other notational simplifications, such as the per-unit system .
A secondary advantage of using a single-line diagram is that the simpler diagram leaves more room for including non-electrical information, for example economic .
When the method of symmetrical components is used, a separate single-line diagram is constructed for each of the positive-, negative- and zero-sequence systems. This simplifies the analysis of unbalanced conditions in a multiphase system. The diagrams show elements that have different impedances for different phase sequences . For example, a generator will, as a rule , have different positive- and negative-sequence impedances, and some transformer winding connections block zero-sequence currents. An asymmetric system can be decomposed into three single-line diagrams, one for each sequence, and connected to show how the asymmetric components add up in each part of the system.